Technical Data Sheet
 |
 Model Type |
PRISM 600-12P |
PRISM 1K-24P |
PRISM 2K-48P
|
Power Rating: |
600VA |
1000VA |
2000VA |
AC Input |
Voltage |
140~300V |
220V ± 25% |
Frequency: |
50Hz OR 60Hz ± 5Hz |
 AC Output |
Voltage Regulation: |
230V ± 8%
|
220 ± 5% |
Output Frequency: |
50Hz OR 60Hz ± 0.5Hz
|
50/60Hz ± .25Hz |
Waveform: |
Synthesized Sine Wave |
Load Power Factor: |
0.8 Lagging |
Transfer Time: |
Line to inverter 2 milliseconds Inverter to line 1 millisecond |
Indicators: |
Mains Normal & Low Battery |
Alarms: |
On battery intermittent beep every 4 seconds.
Battery low intermittent beep every 1 second.
Overload continuous beep. |
Protection |
Spike Protection: |
480 Joules, 2ms |
320 Joules, 2ms
|
Overload: |
UPS automatic shutdown if overload exceeds 110% of nominal
at 60 sec and 130% at 3 sec. |
Input: |
Fuse for overload & short circuit protection |
10Base-T Cable port: |
Network (UTP, RJ-45) compatible jacks |
Surge Protection: |
Meet IEEE 587 standard |
Short Circuit: |
UPS output is cut off instantaneously or input fuse protection |
Battery |
Type: |
Sealed, Maintenance-free lead acid battery. |
Battery Runtime: |
15-30 minutes |
Extended Battery Runtime: |
No |
Yes |
Yes |
Protection: |
Automatic self-test & deep discharge protection, weak battery indicator.
|
Recharge Time: |
4 hours to 90% |
Environment |
Temperature: |
0° C to 48° C |
Humidity: |
0% to 95% (non-condensing) |
Elevation: |
3500 meters max. Elevation170 x 225 x 450 |
Audible Noise: |
<40dBA (1 meter from surface) |
Mechanical
|
Weight (Kgs): |
5.9
|
14.8
|
26.2
|
Dimensions (w X d X h) mm: |
97 x 135 x 320
|
130 x 192 x 382
|
170 x 225 x 450 |